倍加福齐纳式安全栅模块
安全栅是倍加福的核心产品。我们提供全系列的产品用于保护危险区中的电信号。本质安全模块主要由限能齐纳栅和电气隔离组成。倍加福公司产品满足各种应用,适合多种安装。
Zener Barriers – Cost Saving and Easy Mounting Ex-Protection
Zener barriers provide cost saving Ex-protection for various applications in process automation systems. The amount of energy transferred to the hazardous location is limited to a safe level incapable of igniting the explosive atmosphere.
Z-system zener barriers from Pepperl+Fuchs are directly mounted on a 35 mm DIN-Rail. Through accessories, the required grounding can be done directly on the DIN mounting rail.
- Fast mounting on the DIN-rail
- Grounding directly connected with DIN-rail
- Separation of field loop by removing the fus
Z-system zener barriers are available with high density up to 2 channels / 12,5 mm width. Variants with field replaceable fuses provide a convenient means of disconnecting or open-circuiting the instrument loop without interfering with the wiring, making commissioning and maintenance operations much easier.
General specifications
Z828.H.F相关技术参数:
General specifications
Type
DC version, negative polarity
Electrical specifications
Nominal resistance
240 Ω
Series resistance
max. 273 Ω
Fuse rating
50 mA
Hazardous area connection
Connection
terminals 1, 2
Safe area connection
Connection
terminals 7, 8
Working voltage
max. 27 V , 26.5 V at 10 µA
Conformity
Degree of protection
IEC 60529
Ambient conditions
Ambient temperature
-20 ... 60 °C (-4 ... 140 °F)
Storage temperature
-25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Degree of protection
IP20
Connection
screw terminals , max. core cross-section 2 x 2.5 mm2
Mass
approx. 150 g
Dimensions
12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch)
Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EC-Type Examination Certificate
BAS 00 ATEX 7096 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection
II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2]
Statement of conformity
TÜV 99 ATEX 1484 X , observe statement of conformity
Group, category, type of protection, temperature class
II 3G Ex nA II T4 [device in zone 2]
Directive conformity
Directive 94/9/EC
EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010
International approvals
FM approval
Control drawing
116-0118
UL approval
Control drawing
116-0355 (cULus)
CSA approval
Control drawing
116-0119
倍加福齐纳式安全栅模块产品型号参考:
Z705 Z779.F Z887 Z966.F
Z710 Z779.H Z888 Z966.H
Z713 Z779.H.F Z896 Z967
Z715.F Z786 Z905 Z978
Z722 Z787 Z910 Z040
Z728 Z787.F Z915 Z041
Z728.CL Z787.H Z915.1K Z042
Z728.F Z787.H.F Z928 Z810.CL
Z728.H Z788 Z954 Z813
Z728.H.F Z788.H Z955 Z857
Z731 Z788.R Z960 Z864
Z755 Z789 Z960.F Z865
Z757 Z796 Z961 Z865.F
Z764 Z810 Z961.F Z872
Z765 Z822 Z961.H Z879.F
Z765.F Z828.H.F Z964 Z879.H.F
Z772 Z878 Z965 Z886
Z778 Z888.H Z966 Z887.F
Z887.H.F Z922 Z715.1K Z715
Zener barriers provide cost saving Ex-protection for various applications in process automation systems. The amount of energy transferred to the hazardous location is limited to a safe level incapable of igniting the explosive atmosphere.
Z-system zener barriers from Pepperl+Fuchs are directly mounted on a 35 mm DIN-Rail. Through accessories, the required grounding can be done directly on the DIN mounting rail.
- Fast mounting on the DIN-rail
- Grounding directly connected with DIN-rail
- Separation of field loop by removing the fus
Z-system zener barriers are available with high density up to 2 channels / 12,5 mm width. Variants with field replaceable fuses provide a convenient means of disconnecting or open-circuiting the instrument loop without interfering with the wiring, making commissioning and maintenance operations much easier.
General specifications
Z828.H.F相关技术参数:
General specifications | ||
Type | DC version, negative polarity | |
Electrical specifications | ||
Nominal resistance | 240 Ω | |
Series resistance | max. 273 Ω | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | max. 27 V , 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals , max. core cross-section 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BAS 00 ATEX 7096 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] | |
Statement of conformity | TÜV 99 ATEX 1484 X , observe statement of conformity | |
Group, category, type of protection, temperature class | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2012, EN 60079-11:2012, EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |